| Test |
Purpose |
Procedure |
Results |
| Thermal Resistance |
Determines insulating
properties of the panels |
ASTM C236
Guarded Hot Box |
Good R values for an HCFC Foam System
(see published values for panel type and thickness) |
|
|
|
|
Air
Leakage |
Measures air leakage
through the panel joints |
ASTM E283
Chamber Method |
The leakage rate for panel will not exceed
0.01 CFM/SF at 40 psf pressure differential |
|
|
|
|
Water
Penetration |
Measures water leakage
through the panel joints |
ASTM E331
Chamber Method |
No water penetration at pressure differential
of 50 psf |
|
|
|
|
| Strength |
Determines the load/span
properties of the roof and wall
panels |
ASTM E72
Chamber Method |
Panel load/span and deflection tables
are available |
|
|
|
|
Surface
Burning |
Determines the surface
burning characteristics of the
core and panels |
Underwriters
Laboratories UL 723
(ASTM E84) |
Core Material (5")
Flame Spread 20*
Smoke Developed 400
Finished Panel
2" to 5" Wall Panel
Flame Spread 15*
Smoke Developed 250 - 450 |
Factory Mutual
ASTM E84 |
Core Material (5")
Flame Spread 25*, Smoke Developed 180 |
|
|
|
|
Room
Fire Test |
Evaluates the burning of
roof and wall panels in a room
configuration |
Factory Mutual
STD. 4880 (1994)
(UBC 26-3) |
Panel is rated
Class 1 to 30 ft. high, 5 in. max. thickness |